DC Disconnect Switch Sizing for 1000V PV Strings

Key Takeaway
A 1000 V PV string disconnect is a DC switch-disconnector sized to the string’s cold open-circuit voltage and to a continuous current built from short-circuit current. In the worked example here, maximum circuit current is 1.25 times Isc, and the disconnect continuous rating is taken as 1.25 times that maximum circuit current. A 1500 V combiner output is a different voltage, a different current, and often a different utilization category. The datasheet for the part number has to meet the result. This page does not assign a Weltrus ampere frame.
Table of Contents
When a Round Ampere Number Is Treated as the Spec
String disconnects are often ordered from a single number: 32 A, or whatever frame the last project used. That number does not say whether the device is rated 1000 V DC or 1500 V DC, whether it breaks load or only isolates after the inverter has stopped, or whether one pole or both poles open. A switch that was correct on a short rooftop string can be outside its voltage rating on a longer string at a cold site, even when the current is still small.
The other mix-up is the combiner. A 1000 V string disconnect sees one string, or a few strings, at a voltage the designer has kept at or below 1000 V after temperature correction. A 1500 V utility combiner output sees many parallel strings and a higher open-circuit voltage. Current scales with the number of strings. Voltage scales with modules in series and with cold temperature. Using the string switch on the combiner output fails both checks at once.
Size the circuit, then ask the datasheet of a part number whether it covers that circuit. Do not start from a Weltrus catalog ampere and work backward. This article does not publish one.
Voltage, Current, Poles, Category, and Enclosure
Five ratings have to be true together. Missing one of them is how a switch looks acceptable on a spreadsheet and is rejected in review.
Voltage. The DC voltage rating must be at least the maximum array voltage. Maximum voltage is not the standard-test open-circuit voltage. Cell voltage rises as temperature falls. Calculate it. A 1000 V label covers the string only when the cold open-circuit voltage is less than or equal to the DC rating on the datasheet at the site altitude. A 1500 V label is a different device.
Current. Two factors appear in US practice under NEC 690.8, and a 1.25 irradiance factor is also the usual design current in IEC array rules. This article uses both steps and labels them. First, maximum circuit current equals 1.25 times the module short-circuit current, summed across strings that are in parallel on that switch. The 1.25 covers irradiance above 1000 watts per square meter. Second, because that current is continuous, the disconnect continuous rating in this worked example is 1.25 times the maximum circuit current. That is 1.56 times Isc when a single string is the whole circuit. If the adopted code edition or the listing tells you to stop after the first 1.25, follow that rule and say so on the calculation sheet. Do not silently drop a factor.
Poles and category. An ungrounded string with a transformerless inverter is normally switched on both positive and negative. Utilization category tells you whether the device may open PV current. Under IEC 60947-3, DC-PV1 fits opening a string at string current. DC-PV2 fits a point where other parallel strings can feed the switch, which is the combiner output. An off-load isolator is not a load-break switch. Write the category into the RFQ.
Enclosure. An outdoor string switch lives in sun and rain. The current rating is valid inside the ambient and the enclosure the datasheet assumes. A higher internal temperature can require a derate. Use the curve printed for that part number. This article does not invent a derate percentage.
Worked Sizing for a 1000 V String and a 1500 V Combiner
The module in this table is an example so the arithmetic is visible. It is not a Weltrus module rating. Assumptions, used in every row: Isc = 13.8 A at standard test conditions, Voc = 49.5 V, open-circuit temperature coefficient = -0.25 percent per degree C, lowest cell temperature = -10 degrees C. Standard test cell temperature is 25 degrees C, so the temperature difference is 35 degrees. The voltage factor is 1 + (0.25 / 100) x 35 = 1.0875. Formula: maximum voltage = (modules in series) x 49.5 V x 1.0875. Maximum circuit current = 1.25 x (strings in parallel) x 13.8 A. Disconnect continuous current in this article = 1.25 x maximum circuit current.
| Step | 1000 V class, one string | 1500 V class, combiner output |
|---|---|---|
| Series modules, and strings in parallel | 18 series, 1 string | 26 series, 12 strings in parallel |
| Open-circuit voltage at 25 degrees C | 18 x 49.5 V = 891 V | 26 x 49.5 V = 1287 V |
| Cold open-circuit voltage | 891 V x 1.0875 = 968.96 V | 1287 V x 1.0875 = 1399.6 V |
| Maximum circuit current, 1.25 x Isc total | 1.25 x 13.8 A = 17.25 A | 1.25 x 12 x 13.8 A = 207 A |
| Disconnect continuous current used here, 1.25 x maximum circuit current | 1.25 x 17.25 A = 21.56 A | 1.25 x 207 A = 258.75 A |
| What the datasheet must show | DC rating at least 968.96 V and at least 21.56 A continuous, category DC-PV1 if it only opens this string | DC rating at least 1399.6 V and at least 258.75 A continuous, category DC-PV2 if parallel strings can feed the switch |

Read the 1000 V column as a string device. Cold voltage is 968.96 V, so a switch whose datasheet rates it 1000 V DC can cover the voltage in this example, at the altitude where that 1000 V rating is valid. The current the switch must carry continuously, under the second 1.25 used here, is 21.56 A. A larger frame is a catalog choice the datasheet may offer. This page does not name a Weltrus frame and does not round 21.56 A up to a house rating.
Read the 1500 V column as a different device. Cold voltage is 1399.6 V, which is already above any 1000 V DC rating. Twelve parallel strings raise maximum circuit current to 207 A, and the continuous figure used here is 258.75 A. A string isolator sized near 21.56 A does not carry 258.75 A, and a 1000 V device does not cover 1399.6 V. The combiner switch is selected from a datasheet that states both the voltage and the current at DC-PV2, or at the category the manufacturer assigns to that duty.
Change an assumption and the table moves. A colder cell temperature than -10 degrees C raises the 1.0875 factor. A larger temperature coefficient than 0.25 percent per degree raises it as well. One extra module in series on the 18-module string may push cold voltage through 1000 V. Add the module only after you recompute. Two extra parallel strings on the combiner add 1.25 x 2 x 13.8 A = 34.5 A to maximum circuit current, and another 1.25 on top of that if you keep this article’s second factor.
Conductor and fuse sizing can use the same 1.56 factor and then jump to the next standard fuse size. That fuse size is not the disconnect frame. A 25 A fuse next to a string does not mean the switch is a 25 A Weltrus part. It means the overcurrent device was chosen from the conductor rules. The switch still needs its own DC current and voltage lines on its own datasheet.
Poles, Outdoor Enclosures, and Altitude
Pole count follows the grounding scheme. On a floating array, open both polarities so a single remaining conductor is not left tied to the inverter. A grounded array follows the code and the inverter manual for which pole must open. Do not copy a single-pole DC switch from an older grounded design onto a transformerless string without checking that manual.
The enclosure rating is part of the switch, not a separate box you ignore. Outdoor rooftop gear is commonly specified NEMA 3R, NEMA 4X, or IP65, depending on the market and on whether washdown or coastal corrosion is in the spec. The handle needs a lockout for maintenance. Internal temperature in full sun can sit well above the outdoor air temperature. If the datasheet derates current above a stated ambient, apply that curve inside the enclosure temperature you expect, not at a mild laboratory ambient.
Altitude cuts voltage withstand and sometimes current. Many IEC sheets state ratings up to 2000 m and then publish a correction. Use the correction for the part number. A 1000 V rating at sea level is not automatically a 1000 V rating at 3000 m. The same warning applies to a 1500 V combiner switch. Recompute after you know the site elevation, and keep the cold-voltage result under the derated voltage, not under the sea-level headline.
Polarity marks on the terminals matter. Photovoltaic current is one direction, from the array toward the inverter, which is simpler than a battery contactor that must break both ways. Line and load markings on a magnetically blown switch still have to match the sheet. Reversing them can cancel the arc control the breaking test used.
What This Sizing Does Not Decide
- It does not publish a Weltrus disconnect ampere rating. 21.56 A and 258.75 A are example-circuit results. The part number datasheet is the rating.
- It does not replace the project code. The second 1.25 is labeled. If the adopted NEC edition, the IEC design guide, or the listing uses one factor, follow that factor and show it.
- It does not make a contactor into a code disconnect. A contactor can provide a remote open inside its break rating. A disconnecting means still has to be the device the code and the listing require.
- It does not size the inverter, the string fuse, or the wire by itself. Those calculations share Isc and voltage, then apply their own rules and terminal limits.
- It does not allow a 1000 V string switch on a 1500 V combiner because both objects are called DC disconnects.
Send the String Counts and the Coldest Cell Temperature
Share modules in series, strings in parallel, module Isc and Voc, the temperature coefficient, and the site. Weltrus will check those numbers against the datasheet of the disconnect part number, including voltage, current, and utilization category.
Frequently Asked Questions
Is 1.25 times Isc the same number as the disconnect current rating?
Not in the worked example on this page. Maximum circuit current is 1.25 times Isc, which covers irradiance above the standard test. This article then sizes the disconnect continuous rating to 1.25 times that maximum circuit current, because PV current is treated as continuous. The second step is a labeled assumption. The adopted code and the listing of the part number control if they require a different factor.
Can a 1000 V string disconnect be used on a 1500 V combiner output?
No. The combiner output can sit above 1000 V once cold open-circuit voltage is calculated, and it carries the sum of the parallel strings. A switch rated 1000 V DC does not become a 1500 V device because the current rating looks large enough. Voltage, current, and utilization category all have to fit the datasheet.
What is the difference between DC-PV1 and DC-PV2?
Both are utilization categories for photovoltaic switch-disconnectors in IEC 60947-3. DC-PV1 is the duty of opening a string where the current is that string current. DC-PV2 is the harder duty in which current from other parallel strings can feed the switch, which is the usual combiner-output case. The datasheet has to name the category you need at the voltage of the array.
Do you size the disconnect to the inverter input current?
Size a source-circuit disconnect to the PV current available from the modules, using the formulas on this page, not to a lower inverter operating current. The inverter current limit does not reduce the short-circuit current the switch must be rated to carry and, if it is a load-break device, to interrupt.
Does this article publish a Weltrus disconnect amp rating?
No. The 21.56 A and 258.75 A figures are results for the labeled example modules and string counts. They are the currents the example circuits require. The datasheet for the part number you buy either meets those currents at the required DC voltage or it does not. Ask for that page.