FXM8LC Series Residual Current Operated Circuit Breaker with Intelligent Monitoring

Key Advantages

  • Comprehensive protection functions: Residual current, overload, short circuit, phase loss, overvoltage, undervoltage, unbalance, and zero line loss protection
  • Intelligent monitoring: LCD display with real-time load current, residual current display, action status indication, and trip data display
  • Automatic reclosing: Smart automatic reclosing function with adjustable reclosing interval time (20-60s)
  • Wide current range: 125A to 800A across 125/250/400/630/800 frame sizes
  • High breaking capacity: M type (35-65kA) & H type (65-85kA) for different applications
  • Communication capability: Optional RS-485 communication with multiple protocols for remote monitoring and control
  • Compact design: Integrated electric operating mechanism reduces installation space and simplifies wiring
  • Flexible pole configurations: 3P+N (zero wire cannot be disconnected) and 4P (zero wire can be disconnected)
  • Advanced fault recording: Records trip type, cause, time, voltage, current, and leakage data for detailed analysis
  • Category B selective: Enables selective coordination with upstream and downstream protection devices
  • Multiple setting options: Configurable operating current, breaking time, and main circuit current according to actual requirements
  • Pluggable lightning protection module: Optional lightning protection module for enhanced surge protection
GB/T 14048.2 GB/T 14048.4 GB/T 32902 GB/T 22387 Category B

The FXM8LC series residual current operated circuit breaker is an advanced protection device designed for AC 50Hz, 400V distribution systems. Featuring intelligent monitoring, automatic reclosing, and comprehensive protection functions, it provides precise protection for circuits and electrical equipment against overload, short circuit, grounding faults, and indirect personal contact. The LCD display allows real-time monitoring of load current and residual current, while the intelligent control circuit enables fault cause tracking and historical data recording. With breaking capacities up to 85kA and current ratings to 800A, it offers reliable performance in demanding industrial and commercial applications. The optional RS-485 communication capability enables integration into smart power distribution systems for remote parameter adjustment and information query.

Basic Specifications

Parameter Specification Details
Product Name FXM8LC Series Residual Current Operated Circuit Breaker With intelligent monitoring
Rated Insulation Voltage AC 1000V
Rated Impulse Withstand Voltage 8kV / 12kV 125/250A: 8kV; 400/630/800A: 12kV
Rated Operating Voltage AC 380/400/415V 50Hz frequency
Rated Current Range 125A – 800A Across 5 frame sizes
Rated Residual Operating Current 0.06A / 0.1A / 0.2A Optional settings
Ultimate Non-driving Time 0-0.5s Delay type with automatic tracking
Number of Poles 3P+N, 4P Various N-pole configurations
Breaking Capacity Type M Type & H Type M: Standard; H: High breaking
Ultimate Breaking Capacity (Icu) 35-85kA Depending on frame and type
Service Breaking Capacity (Ics) 50-85kA Depending on frame and type
Short-time Withstand (Icw) 5-10kA for 1s Depending on frame size
Residual Short-circuit Making/Breaking (IΔm) 25% of Icu
Selective Category Category B IEC/EN 60947-2
Reclosing Interval Time 20-60s Manual closing not limited
Display Type LCD / Digital Y: LCD; S: Digital

Frame Size & Breaking Capacity

Frame Current In(A) Overload Long Delay IR(A) Icu (kA) Ics (kA) Icw (kA/1s) Impulse Voltage (kV)
125 (0.4~1)In M50 / H85 M50 / H85 5 8
250 (0.4~1)In M65 / H85 M65 / H85 10 8
400 (0.4~1)In M65 / H85 M65 / H85 10 12
630 (0.4~1)In M35 / H65 M50 / H65 10 12
800 (0.4~1)In M50 / H65 M50 / H65 10 12

Note: M = Standard breaking capacity, H = High breaking capacity. Overload long delay setting range is (0.4~1)In.

Pole Configuration Options

Pole Configuration Description Application
3P+N Three-pole four-wire, zero wire cannot be disconnected Systems where neutral line must remain connected
4P Four-pole, zero wire can be disconnected Systems requiring complete circuit isolation

Protection Functions

Residual Current

0.06-0.2A

Adjustable

Grounding protection

Overload Long Delay

(0.4~1)In

Adjustable IR

Thermal protection

Short Circuit

Short delay

Instantaneous

Fast response

Phase Loss

Three-phase

Protection

Motor safety

Overvoltage

Adjustable

With delay

Equipment protection

Undervoltage

Adjustable

With delay

Equipment protection

Unbalance

Phase

Protection

Equipment safety

Zero Line Loss

Neutral

Protection

Safety critical

Intelligent Features

Feature Description Benefit
LCD Display Digital LCD screen with real-time data Easy monitoring and status indication
Automatic Reclosing Automatic circuit reclosing after fault clearing Reduces downtime and manual intervention
Residual Current Display Real-time leakage current monitoring Early warning of insulation degradation
Load Current Display Real-time load current monitoring Load management and optimization
Trip Data Recording Records trip type, cause, time, voltage, current, leakage Facilitates fault analysis and troubleshooting
Fault Cause Tracking Monitors and displays cause of fault trip Quick fault identification and resolution
Historical Data Recording Stores up to 113 trip records Comprehensive event history for analysis
RS-485 Communication (Optional) Remote monitoring and control via RS-485 Integration into smart power systems

Normal Working & Installation Conditions

  • Ambient temperature: -20°C to +40°C (operating), lower limit -20°C, upper limit +40°C
  • 24h average temperature: Not to exceed +35°C
  • Relative humidity: Maximum 50% at +40°C, higher humidity at lower temperatures (special measures for condensation)
  • Altitude: Not to exceed 2000m
  • Pollution level: Level 3
  • Installation orientation: Vertical mounting (maximum inclination ±5°)
  • Environment: No rain or snow erosion
  • Installation category: Category III (main circuit), Category II (auxiliary and control circuits)
  • External magnetic field: Not to exceed 5 times the geomagnetic field in any direction
  • Frequency: AC 50Hz

Operation Interface Features

Main Menu Functions

  • Real-time display interface
  • Parameter setting interface
  • Parameter display
  • Trip record query
  • Number of trips statistics
  • Self-check setting
  • Factory maintenance

Control Buttons

  • Up/Down: Move cursor or adjust settings
  • Menu: Enter submenu
  • Return: Return to previous interface
  • Set: Move setting item cursor
  • Confirm: Enter/exit setting status, save parameters

Recommended Applications

Application Type Description BENEFIT
Three-phase Four-wire Systems AC 50Hz, 400V distribution networks with neutral point directly grounded Comprehensive protection for TN-S, TN-C-S systems
Industrial Power Distribution Factory and industrial facility power protection Reliable protection with intelligent monitoring
Commercial Buildings Office buildings, shopping malls, hotels Enhanced safety with ground fault protection
Data Centers Critical infrastructure power protection High reliability with automatic reclosing
Motor Control Centers Motor protection and control systems Phase loss and overload protection
Smart Grid Systems Intelligent power distribution with communication Remote monitoring and control capability

Compliance Standards

GB/T 14048.2

Circuit Breakers

Low-voltage

Switchgear

GB/T 14048.4

Contactors

Motor Starters

IEC 60947-4-1

GB/T 32902

Residual Current

Devices

Protection

GB/T 22387

Residual Current

Operated Devices

Safety

Recommended Applications

  • Three-phase four-wire distribution systems
  • Industrial power distribution
  • Commercial building power protection
  • Data center power systems
  • Motor control centers
  • HVAC system protection
  • Smart grid applications
  • Renewable energy systems
  • Water treatment plants
  • Healthcare facility protection

Quick Specifications

  • Current range: 125A – 800A
  • Voltage rating: AC 380/400/415V
  • Frequency: 50Hz
  • Residual current: 0.06-0.2A
  • Breaking capacity: 35-85kA Icu
  • Poles: 3P+N, 4P
  • Category: Category B selective
  • Display: LCD / Digital optional
  • Communication: RS-485 optional
  • Standards: GB/T 14048.2/4, GB/T 32902, GB/T 22387

Ordering Information

When ordering, please specify:

  • Model and specification (FXM8LC)
  • Frame current rating (125/250/400/630/800A)
  • Number of poles (3P+N or 4P)
  • Breaking capacity level (M or H)
  • Display type (LCD or Digital)
  • Residual current setting (0.06/0.1/0.2A)
  • Communication requirement (Yes/No)
  • Accessories and options

Example: FXM8LC-250M/3310 250A AC400V 0.1A LCD with RS-485

Contact Information

Hangzhou Weltrus New Energy Technology Co., Ltd.

Block D, Ocean International Center
333 Yuanjian Street, Hangzhou
Zhejiang, China

Tel/WhatsApp: +86 13735502672

Email: [email protected]

Contact Us

WhatsApp

+86-13735502672

Talk to our experts

  • We will contact you within 12 hours
  • Don’t worry, we hate spam too!